Warning Message

HISTORY_XDB;DB Error (4001): Source: Microsoft OLE DB Provider for ODBC Drivers, Description: [Microsoft][ODBC Driver Manager] Data source name not found and no default driver specified

Related ProductsBMS Server 2.0
DescriptionThe historical database could not be reached through the ODBC driver.
Causes
  1. The BMS Server was (accidentially) configured to use an ODBC connection, which is not the default installation setting.
  2. The configured ODBC DSN could not ne found.
Resolutions
  1. Uncheck the parameter BMS Studio / Server / System configuration / XDB / Enable DSN and restart the BMS Server.