Warning Message

BACnet;Invalid data type for item <IdemID>. BACnet Object Type not supported.

Related ProductsBMS Server 2.0
DescriptionThe BACnet driver was not able to map the given server item with the given type.
Causes
  1. The object type provided in the BACnet mapping table is not suitable for the given server item.
Resolutions
  1. Change the object type in BACnet / Object mapping definitions or leave the field empty for auto-typing by the BACnet driver.